TECDrive20-EU Series Inverter Function parameters
-46-
Function
code
Name
Description
Default
Modify
Setting range: 0.060.0s
P01.24
Delay of
stopping speed
Setting range: 0.0100.0s
0.0s
P01.25
0Hz output
Select the 0Hz output of the inverter.
0: No voltage output
1: With voltage output
2: Output at stop DC brake current
0
P02 group Motor 1 parameters
Function
code
Name
Description
Default
Modify
P02.01
Rated power of
async-motor
0.13000.0kW
Depend
on
model
P02.02
Rated
frequency of
async-motor
0.01HzP00.03
50.00Hz
P02.03
Rated speed of
async-motor
160000rpm
Depend
on
model
P02.04
Rated voltage
of async-motor
01200V
Depend
on
model
P02.05
Rated current
of async-motor
0.86000.0A
Depend
on
model
P02.06
Stator resistor
of async-motor
0.001–65.535Ω
Depend
on
model
P02.07
Rotor resistor
of async-motor
0.001–65.535Ω
Depend
on
model
P02.08
Leakage
inductance of
async-motor
0.16553.5mH
Depend
on
model
P02.09
Mutual
inductance of
async-motor
0.16553.5mH
Depend
on
model

Table of Contents