TECDrive20-EU Series Inverter Function parameters
-45-
wake-up-from-sleep delay time. When the
running frequency of the inverter is lower than
the lower limit, the inverter becomes standby.
When the set frequency exceeds the lower limit
one again and it lasts for the time set by P01.20,
the inverter runs automatically.
Set frequency curve:
Running frequency curve:
Run
Sleep
t2
t1
Run
Frequency
lower limit f0
Frequency f
Time t
Coast to
stop
t1 < P01.20, the inverter does not run
t1+t2 ≥P01.20, the inverter runs
Setting range: 0.0–3600.0s (valid when
P01.19=2)
This function can enable the inverter to start or
not after power off and power on.
0: Disabled
1: Enabled, if the starting need is met, the
inverter will run automatically after waiting for the
time defined by P01.22.
The waiting
time of restart
after power off
The function determines the waiting time before
the automatic running of the inverter when
powering off and powering on.
Output frequency
Running
Power off
Power on
Running
t
t1 t2
t1=P01.22
t2=P01.23
Setting range: 0.0–3600.0s (valid when
P01.21=1)
The function determines the brake release after
the running command is given, and the inverter is
in a stand-by state and wait for the delay time set
by P01.23