TECDrive20-EU Series Inverter Function parameters
-40-
Function
code
Name
Description
Default
Modify
function.
2. Restoring default values (factory test mode) will
restore the parameters to the corresponding
standard version. Non-professionals shall
exercise caution when using this function.
P01 group Start and stop control
Function
code
Name
Description
Default
Modify
P01.00
Start mode
0: Start-up directly: start from the starting
frequency P01.01
1: Start-up after DC braking: start the motor from
the starting frequency after DC braking (set the
parameter P01.03 and P01.04). It is suitable in
the cases where reverse rotation may occur to
the low inertia load during starting.
2: Start after speed tracking 1
3: Start after speed tracking 2
The direction and speed will be tracked
automatically for the smoothing starting of
rotating motors. It suits the application with
reverse rotation when big load starting.
Note: This function is only available for the
inverters≥4kW.
0
P01.01
Starting
frequency of
direct start-up
Starting frequency of direct start-up means the
original frequency during the inverter starting.
See P01.02 for detailed information.
Setting range: 0.0050.00Hz
0.50Hz
P01.02
Hold time of
the starting
frequency
Set a proper starting frequency to increase the
torque of the inverter during starting. During the
retention time of the starting frequency, the
output frequency of the inverter is the starting
frequency. And then, the inverter will run from the
starting frequency to the set frequency. If the set
frequency is lower than the starting frequency,
the inverter will stop running and keep in the
stand-by state. The starting frequency is not
limited in the lower limit frequency.
0.0s