TECDrive20-EU Series Inverter Function parameters
-87-
Low frequency
integral time
(Ti)
Low frequency
differential time
(Td)
Low point
frequency of
PID parameter
switching
0.00Hz–P09.21
When the ramp frequency is no greater than
P09.20, current PID parameters are
P09.17–P09.19. When the ramp frequency is no
less than P09.21, current PID parameters are
P09.04–P09.06. The medium frequency range is
the linear interpolation values between the two
PID parameter groups.
High point
frequency of
PID parameter
switching
P10 group Simple PLC and multi-step speed control
0: Stop after running once; the inverter stops
automatically after running for one cycle, and it
can be started only after receiving running
command.
1: Keep running in the final value after running
once. The inverter keeps the running frequency
and direction of the last section after a single
cycle.
2: Cyclic running; the inverter enters the next
cycle after completing one cycle until receiving
stop command and stops.
Simple PLC
memory
selection
0: No memory after power-off
1: Memory after power-off; PLC memories its
running step and frequency before power-off.