TECDrive20-EU Series Inverter Function parameters
-74-
Refer to P00.11 and P00.12 for detailed
definition.
The first group of ACC/DEC time is the factory
default one.
Setting range: 0.0–3600.0s
This parameter is used to define the reference
frequency during jogging.
Setting range: 0.00Hz–P00.03 (the max.
frequency)
Jogging
running
acceleration
time
The jogging acceleration time means the time
needed if the inverter runs from 0Hz to the max.
frequency.
The jogging deceleration time means the time
needed if the inverter goes from the max.
frequency (P00.03) to 0Hz.
Setting range: 0.0–3600.0s
Jogging
running
deceleration
time
When the set frequency is in the range of
jumping frequency, the inverter will run at the
edge of the jumping frequency.
The inverter can avoid the mechanical
resonance point by setting the jumping
frequency. The inverter can set three jumping
frequency. But this function will be invalid if all
jumping points are 0.
Set frequency f
Time t
Jump
frequency 2
1/2*Jump
frequency range 2
1/2*Jump
frequency range 2
Jump
frequency 1
1/2*Jump
frequency range 1
1/2*Jump
frequency range 1
Jump
frequency 3
1/2*Jump
frequency range 3
1/2*Jump
frequency range 3
Setting range: 0.00–P00.03 (the max. frequency)
Jumping
frequency
range 1
Jumping
frequency
range 2
Jumping
frequency
range 3
This function applies to the industries where