command, Cn-02)
1 : Output frequency (10.V/MAX.
output frequency)
2 : Output current (10.V/input rated
current)
3 : Output voltage (10.V/input
voltage, Cn-01)
4 : DC voltage
(10.V/400.V or 10.V/800.V)
00
Sn-34
Multi-Function
Analog Output
Function
Selection
Sn-34= 01
Term. AO2 O/P Freq.
5 : External analog input command
VIN (0.~10.V/0.~10.V)
6 : External analog input command
AIN (0.~10.V/4.~20.mA)
7 : Multi-function analog input
(AUX) (10.V/10.V)
8 : PID control input
9 : PID control output1
10:PID control output2
11:Communication Control
01
94
Multi-
function
Analog
Output
Selection
Sn-35
Pulse Output
Multiplier
Selection
Sn-35= 1
Pulse Mul. 6
When multi-function output terminal
(DO1,DO2) is set as pulse signal
output
0:1F 1:6F 2:10F 3:12F 4:36F
194
Sn-36 Inverter Address
Sn-36= 01
Inverter Address
Inverter address can be set as 1~31 01
Sn-37
RS-485 Comm.
Baud Rate
Setting
Sn-37= 1
Baud rate 2400
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
1
Sn-38
RS-485 Comm.
Transmission
Parity Setting
Sn-38= 0
Reversed Bit
0 : no parity
1 : even parity
2 : odd parity
0
RS-485
Commu-
nication
Function
Sn-39
RS-485 Comm.
Fault Stop
Selection
Sn-39= 0
1st. Dec. stop
0 : deceleration to stop (Bn-02)
1 : coast to stop
2 : deceleration to stop (Bn-04)
3 : continue to run
0
95