p
Model 880 DEPOSITION CONTROLLER
y
SECTION 3.XX
e page 95 of 275 ^
Pressing the NEXT FILM key brings forth the numeric entry screen that is used to select the next active
film. BAcK returns the previous screen and discards the entry, if any. ENTer accepts the digit[s] entered as
the next active film and returns to the previous screen.
If 14 were entered, upon return to the runtime screen, the message "Next Film: 14" would appear as shown
below.
Programming the unit for non-sequencing involves the same type of communications and I/O setups,
system configuration, and film parameter modifications.
Process programming does not exist for non-sequencing product use.
An added parameter is added to the film parameter list: Final Thick Limit.
The final thickness, no longer part of process programming, becomes a parameter.
SEQ: active film# is always selected by a process.
non-SEQ: active film# is selected in place of active process# (MAIN menu key label change is apparent
along with non-appearance of the REVIEW PROCESSES key).