p
Model 880 DEPOSITION CONTROLLER
y
SECTION 3.XX
e page 130 of 275 ^
Product programming summary
SECTION 3.22
Summary
In all of the following cases, use BAKs and/or BYEs for a return path. The fixed STATUS key can be used
at any time or point to return to the Run Time screen.
To program for PROCESS NON-SEQUENCING...
Screen Key[s] to press
Run Time fixed MENU
MAIN MENU SERVICE
Service menu SEQ [en]ABLE to NON SEQ + ACCEPT
To program for PROCESS SEQUENCING...
Screen Key[s] to press
Run Time fixed MENU
MAIN MENU SERVICE
Service menu NON SEQ to SEQ [en]ABLE + ACCEPT
To put the Model 880 into TEST MODE...
Screen Key[s] to press
Run Time fixed MENU
MAIN MENU SERVICE
Service menu TEST OFF to TEST ON + ACCEPT
Subsequent power cycling automatically sets TEST MODE to OFF.
To PURGE programmed memory...
Screen Key[s] to press
Run Time fixed MENU
MAIN MENU SERVICE
Service menu AS IS to PURGE + ACCEPT
Exercise CAUTION PLEASE! See cautions in sections 1.8 and 3.19.
To return to FACTORY settings (programmable elements)...
Screen Key[s] to press
Run Time fixed MENU
MAIN MENU SERVICE
Service menu AS IS to PURGE to FACTORY + ACCEPT