Premier 412/816/832 Installation Manual Installation
INS159-13 19
Siren/Bell Operation
When configured as bell operation the output terminals provide up
to 750mA of power for driving bells as shown:
For EN50131 & INCERT Installations the bell Aux/Tamper
must be wired to a zone.
The Siren/Spk output must be enabled for bell
driver (see page 37 for details).
Siren/Spk Supervision
The Siren/Spk output is supervised, if no warning devices are fitted,
either disable Siren Supervision (see page 38 for details) or connect
a 1K resistor between the Siren terminals as shown:
Telephone Line Connections
The control panel has a built in digital communicator and modem,
which is used for communicating with an alarm receiving centre and
for downloading. If either of these features are used, a telephone
line must be connected to the control panel as shown:
Failure to fit an earth cable may prevent proper
operation of the system and will invalidate the
Texecom warranty and product approvals.
Panel Outputs 1 - 8
The control panel has eight programmable outputs, which can be
used to drive auxiliary devices such as relays, LED’s, smoke
detectors etc. The table shows the electrical characteristics for each
output:
Panel Outputs
No
Supervised
Max Current
Type
1
Yes
1 Amp
Switched ve
2
Yes
1 Amp
Switched ve
3
No
100mA
Switched ve
4
No
100mA
Switched ve
5
No
100mA
Switched ve
6
No
100mA
Switched ve
7
No
100mA
Switched ve
8
No
100mA
Switched ve
Output Wiring
The figure below shows some typical wiring examples:
Output Supervision
Panel outputs 1 and 2 are supervised, if either output is unused,
either disable the relevant output supervision (see page 38 for
details) or connect a 1K resistor between the relevant output
terminal and Auxiliary 12V+ as shown: