Programming the Control Panel Premier 412/816/832 Installation Manual
66 INS159-13
Program User 
The Program User option allows the engineer to assign new users
for the alarm system. The number of users (including the engineer)
that are available is as follows:
Premier 412 - 32 Users
Premier 816 - 32 Users
Premier 832 - 64 Users
User 00 is the Engineer and can only be accessed by the engineer
code. User 01 is the Master User which has a default code of 5678.
Neither of these two users can be deleted from the system.
Each user is assigned the following attributes:
Access Code
This is a unique 4, 5 or 6 digit code that is assigned to the user.
The system will allow a mixture of different length Access
codes. The Access code must be entered at a keypad before
the user can operate the alarm system.
User Options 1
See User Options 1 on page 66 for details.
User Options 2
See User Options 2 on page 66 for details.
User Options 3
See User Options 3 on page 67 for details.
User Text (LCD Only)
See User Text on page 67 for details.
When using an LED keypad it is possible to view the next available
user by pressing the key before entering the two digit user
number. This will cause the next available user to be indicated using
the top row of status lights.
User Options 1 
User Options 1 can be enabled or disabled for a selected user so
that the level of access to the system may be altered. The following
options are available:
Enable for Partition 1
On: The user can access Partition 1.
Off: The user cannot access Partition 1.
Enable for Partition 2
On: The user can access Partition 2.
Off: The user cannot access Partition 2.
 Enable for Partition 3 (Premier 816/832 Only)
On: The user can access Partition 3.
Off: The user cannot access Partition 3.
 Enable for Partition 4 (Premier 816/832 Only)
On: The user can access Partition 4.
Off: The user cannot access Partition 4.
 Allow Arming
On: The user can arm the partitions they have been given access
to.
Off: The user cannot arm any partitions.
 Allow Bypassing
On: The user can bypass zones in partitions they have been given
access to.
Off: The user cannot bypass zones.
 Allow Disarming
On: The user can disarm the partitions they have been given
access to.
Off: The user cannot disarm any partitions.
The Engineer code (User 0) can only disarm the system, if
the system was armed with the Engineer code.
 Allow User Functions
On: The user can access the following user functions:
Reset
View Alarm Log
View Service Faults
Enable Chime
Change Own Code
Off: The user cannot access the above user functions.
User Options 2 
User Options 2 can be enabled or disabled for a selected user so
that the level of access to the system may be altered. The following
options are available:
 Enable One Time Use Access Code
On: The Access code can only be used once to arm and disarm
the system. After the Access code has been used to arm the
system it is automatically deleted.
Off: The Access code behaves normally.
 Time Lock Code with Control Timer 1
On: When Control Timer 1 is on, the Access code will not be
accepted by the system. When Control Timer 1 is off, the
Access code will be accepted by the system. For information
on programming Control Timers, see page 36.
Off: The Access code will be accepted at all times.
 Enable Open Reporting
On: The system will report an ‘Open’ condition to the alarm
receiving centre when the Access code is used to disarm one
or more partitions.
Off: The system will not report an ‘Open’ status.
The panel will always send an open signal after an alarm
even if this option is disabled.
 Enable Close Reporting
On: The system will report a ‘Close’ condition to the monitoring
station when the Access code is used to arm one or more
partitions.
Off: The system will not report a ‘Close’ condition.
 Enable User as Duress Code
On: The Access code will report a ‘Duress’ condition to the
monitoring station when the Access code is used.
Off: The Access code behaves normally.
 Activate Door Strike Output
On: When a user Access code is entered, the output type Door
Strike” (see page 49) is activated for 2 seconds.
Off: The user Access code will not activate the Door Strike”
output.
 Allow Global Bell/Sounder Silence
On: This option allows users to silence the bell and internal
sounder for any partition, even if the user is not assigned to