Programming the Control Panel Premier 412/816/832 Installation Manual
28 INS159-13
Enable Instant Strobe
On: The strobe output will trigger immediately the zone causes an
alarm.
Off: The strobe output will trigger after the bell delay timer. (Zone
must also be programmed for Delayed Bell).
Enable User Chime
On: The keypad sounder and speaker driver will generate a chime
tone when zone is violated in the disarmed state.
Off: The zone will respond as normal.
Enable Transmission Delay
On: The on-board communicator will delay the alarm transmission
to the monitoring station when the zone causes an alarm.
Off: The transmission is instant.
Enable Transmission
On: The on-board communicator will report the alarm status to the
monitoring station when the zone causes an alarm.
Off: The alarm status is not reported.
Zone Attributes 2
Zone Attributes 2 can be assigned to a zone to alter its default
operation. The function of each attribute is described as follows:
Enable Manual Bypass
On: The user can bypass the zone.
Off: The user cannot bypass the zone.
Enable Stay Bypass
On: The zone is automatically bypassed when the system is stay
armed.
Off: The zone is not bypassed when stay armed.
Enable Force Arming
On: The user can arm the system/partition with the zone violated.
Off: The zone must be secure before the system/partition can be
armed.
Quick Response Time
On: The zone response time is governed by the Zone Loop
Response Timer (see page 35).
Off: The zone response time is fixed at 250ms.
Enable Cross Zoning
On: When two or more zones are programmed with this attribute,
the system will start the Cross Zone Delay timer after the first
zone is violated. If another Cross Zone is violated before the
timer expires the system will report a Verified Cross Zone
alarm.
Off: The zones report as normal.
Enable Soak Test
On: The zone is selected for soak test. During the soak test period
the zone will not cause an alarm if violated, but the system
will record the event in the log and indicate a Service
Required Fault. This fault condition can only be cleared, by
performing a “Reset” with the Engineer’s code.
Off: The zone responds as normal.
Enable Swinger Shutdown
On: The zone will only rearm at the end of the bell duration
providing the Swing Shutdown limit has not been reached.
Off: The zone always rearms at the end of the bell duration and
subsequent violations of the zone will cause the system to
reactivate the bell and report the alarm to the monitoring
station.
Enable Double Knock
On: When a zone is enabled for Double Knock it will only cause
an alarm when:
a) The zone remains violated for the duration of the “Cross
Zone Time Window”.
b) The zone is violated twice within the “Cross Zone Time
Window”.
c) If any two zones within the same partition with the
“Double Knock” attribute are violated during the “Cross
Zone Time Window”.
Off: The zone responds as normal.
Zone Attributes 3
Zone Attributes 3 can be assigned to a zone to alter its default
operation. The function of each attribute is described as follows:
Change to Delay 1 on Stay Arm
On: The zone will change to a Delay 1 zone type when the system
is Stay armed.
Off: The zone type will not change.
Change to Follower on Stay Arm
On: The zone will change to a Follower zone type when the
system is Stay armed.
Off: The zone type will not change.
Zone Warning
On: The panel will generate an internal alarm when the zone
remains active for 2 minutes during the disarmed state.
Off: The panel will respond as normal.
Auto Reinstate if Force Armed
On: When a zone is force armed (bypassed), it will automatically
be reinstated when the zone is secured.
Off: Force armed zones remain bypassed until the partition is
disarmed.
Disable Keyswitch when Away Armed
On: The keyswitch zone is disabled once the system is Away
armed, i.e., it cannot be used to disarm the selected
partitions.
Off: The keyswitch zone can be used to arm and disarm the
selected partitions.
Disable Exit Faults
On: The zone will not cause the panel to generate a fault tone or
extinguish the “Ready” light, if violated during the exit mode.
Off: The zone behaves as normal.
Truncate Exit Delay
On: When the zone is activated during exit, the panel will truncate
any remaining exit time to zero. This attribute would normally
be used with Delay 1/Delay 2 zone types.
Off: The zone behaves as normal.
Forced Walk Test
On: When arming the system the zone will be indicated as active,
if the zone has not been activated during the “Activity Time
Window”, see page 36. This will force the user to check that
the zone is secure, on activating the zone the system will
clear the indication from the remote keypad and the user may
continue to arm the system. This feature can be used on
detectors that are at risk of being masked or obscured in
some way.
Off: The zone behaves as normal.