MEC 310 GENSET CONTROLLER -
Option J – CANbus J1939
PM077 R1 09/08/20 Page 15 THOMSON TECHNOLOGY
Running detection
During a start sequence the start relay is deactivated, if:
- the speed exceeds the RPM running setting
- the running feedback input is ON, or
- the measured frequency of the generator is above 30Hz, or
- the speed information given by the EIC communication is above the limit
EICoverspeed_6010
During a stop sequence the generator is considered to be stopped, if:
- the speed is below the running setting
- the running feedback input is OFF, or
- the measured frequency of the generator is below 30Hz, or
- the speed information given by the EIC communication is below the limit
EICoverspeed_6010