MEC 310 GENSET CONTROLLER -
Option J – CANbus J1939
PM077 R1 09/08/20 Page 26 THOMSON TECHNOLOGY
MTU MDEC module 302/303 (MTU)
Displayed values
Object
EIC speed
EIC coolant temp.
EIC oil pressure
EIC faults
EIC oil temp.
EIC fuel temp.
EIC charge air pressure
EIC charge air temp.
(or EIC intake manifold 1 temp.)
Alarms
Below is a list of alarms that can be shown on the display. The alarms will be shown in the alarm
window. The alarms can be acknowledged from the display, but they will be visible until the alarm
disappears in the ECM module.
Alarm list Warning Shutdown
MDEC yellow alarm X -
MDEC red alarm - X
Overspeed - X
Low oil pressure X X
High coolant temp. X X
High oil temp - X
High intercooler temp. X -
Defective cool. level switch X -
Low coolant level - X
MDEC ECU failure - X
Write commands to engine controller
None.
The MTU MDEC is not a part of the J1939, therefore the reading of values, alarms
and shutdowns are different.
The Modbus addresses are read only (function code 04h), and are only available
if the option M Modbus RTU is implemented.
MDEC indication “ – “ means that the alarm in question is not supported.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939 and is the answer not in the manual?

THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939 Specifications

General IconGeneral
BrandTHOMSON
ModelMEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939
CategoryController
LanguageEnglish

Related product manuals