EasyManuals Logo

THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939 User Manual

THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939
46 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
MEC 310 GENSET CONTROLLER -
Option J – CANbus J1939
PM077 R1 09/08/20 Page 40 THOMSON TECHNOLOGY
Addr. Content Type
Bit 15 EIC
Power supply high voltage
Alarms, MTU MDEC series – 2000/4000 – module 302 & 303
Alarm, status and measurement table (read only) function code 04h.
Addr. Content Type
1020 EIC alarms, MEC 310
controller
Bit 0 EIC communication error
Bit 2 EIC shutdown
Bit 3 EIC overspeed
Bit 4 EIC coolant water temperature 1
Bit 5 EIC coolant water temperature 2
Bit 6 EIC oil pressure 1
Bit 7 EIC oil pressure 2
1024 EIC alarms, engine
controller
Bit 0 EIC overspeed, shutdown
Bit 1 EIC low oil pressure, warning
Bit 2 EIC low oil pressure, shutdown
Bit 3 EIC low coolant level, shutdown
Bit 4 EIC MDEC ECU failure, shutdown
Bit 5 EIC high coolant temperature, warning
Bit 6 EIC high coolant temperature, shutdown
Bit 7 EIC high intercooler coolant temp, warning
Bit 8 EIC high oil temperature, shutdown
Bit 9 EIC high charge air temperature, shutdown
Bit 10 EIC defect coolant level switch, warning
Bit 11 EIC MDEC yellow alarm, warning
Bit 12 EIC MDEC red alarm, shutdown

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939 and is the answer not in the manual?

THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939 Specifications

General IconGeneral
BrandTHOMSON
ModelMEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939
CategoryController
LanguageEnglish

Related product manuals