PM077 R1 09/08/20 Page 40 THOMSON TECHNOLOGY
Addr. Content Type
Bit 15 EIC
Power supply high voltage
Alarms, MTU MDEC series – 2000/4000 – module 302 & 303
Alarm, status and measurement table (read only) function code 04h.
Addr. Content Type
1020 EIC alarms, MEC 310
controller
Bit 0 EIC communication error
Bit 2 EIC shutdown
Bit 3 EIC overspeed
Bit 4 EIC coolant water temperature 1
Bit 5 EIC coolant water temperature 2
Bit 6 EIC oil pressure 1
Bit 7 EIC oil pressure 2
1024 EIC alarms, engine
controller
Bit 0 EIC overspeed, shutdown
Bit 1 EIC low oil pressure, warning
Bit 2 EIC low oil pressure, shutdown
Bit 3 EIC low coolant level, shutdown
Bit 4 EIC MDEC ECU failure, shutdown
Bit 5 EIC high coolant temperature, warning
Bit 6 EIC high coolant temperature, shutdown
Bit 7 EIC high intercooler coolant temp, warning
Bit 8 EIC high oil temperature, shutdown
Bit 9 EIC high charge air temperature, shutdown
Bit 10 EIC defect coolant level switch, warning
Bit 11 EIC MDEC yellow alarm, warning
Bit 12 EIC MDEC red alarm, shutdown