MEC 310 GENSET CONTROLLER -
Option J – CANbus J1939
PM077 R1 09/08/20 Page 19 THOMSON TECHNOLOGY
Deutz EMR 2 (J1939)
Warnings and shutdowns
J1939 codes
Warning/shutdown list
SPN
FMI
warning
FMI
shutdown
Low oil pressure 100 - 1
Coolant temperature 110 - 0
Overspeed 190 - 0
EIC yellow lamp - X -
EIC red lamp - - X
Write commands to engine controller
•
Engine controls
All the write commands to the engine controller (ex: speed, start/stop, etc.) are enabled in
setting 7563 (EIC Controls).
•
Engine speed
CANbus ID for speed control: 0xc000003. For J1939 TSC1, the source address of the ML-
2 controller is 3.
The speed regulation is enabled in setting 2781 (Reg. output) and 7563 (EIC
Controls).
FMI indication ‘ – ‘ means that the alarm in question is not supported.