EasyManuals Logo

THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939 User Manual

THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939
46 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
MEC 310 GENSET CONTROLLER -
Option J – CANbus J1939
PM077 R1 09/08/20 Page 42 THOMSON TECHNOLOGY
Alarms, Volvo Penta
Alarm, status and measurement table (read only) function code 04h.
Addr. Content Type
1020 EIC alarms, MEC 310
controller
Bit 0 7570 EIC communication error
Bit 1 7580 EIC warning
Bit 2 7590 EIC shutdown
Bit 3 7600 EIC overspeed
Bit 4 7610 EIC coolant water temperature 1
Bit 5 7620 EIC coolant water temperature 2
Bit 6 7630 EIC oil pressure 1
Bit 7 7640 EIC oil pressure 2
1024 EIC alarms (DM 1) Bit 0 EIC overspeed, warning
Bit 1 EIC oil pressure, warning
Bit 2 EIC oil temperature, warning
Bit 3 EIC high coolant temperature, warning
Bit 4 EIC low coolant level, warning
Bit 5 EIC fuel pressure, warning
Bit 6 EIC ECM yellow lamp, warning
Bit 7 EIC ECM red lamp, shutdown
Bit 8 EIC high inlet air temperature, warning
Bit 10 EIC battery voltage, warning
Bit 11 EIC low oil level, warning
Thomson Technology reserves the right to change any of the above.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939 and is the answer not in the manual?

THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939 Specifications

General IconGeneral
BrandTHOMSON
ModelMEC 310#GENSET CONTROLLER OPTION J-CANBUS J1939
CategoryController
LanguageEnglish

Related product manuals