MEC 310 GENSET CONTROLLER -
Option J – CANbus J1939
PM077 R1 09/08/20 Page 37 THOMSON TECHNOLOGY
Alarms, General J1939
Alarm, status and measurement table (read only) function code 04h.
Addr. Content Type
1020 EIC alarms, MEC 310
controller
Bit 0 7570 EIC communication error
Bit 1 7580 EIC warning
Bit 2 7590 EIC shutdown
Bit 3 7600 EIC overspeed
Bit 4 7610 EIC coolant water temperature 1
Bit 5 7620 EIC coolant water temperature 2
Bit 6 7630 EIC oil pressure 1
Bit 7 7640 EIC oil pressure 2