23
6.4.4 Input Parameter Mode
■Input type setting
Character
Name
Description
Initial Value
1
SET1
INP
Setting Mode Selection
Screen
Input Parameter Mode
Settings about Input
2
INP
Input type setting
Setting Range: 00–06, 10, 11
See Input Type Setting Table for detail
00
Input Type Setting Table
Setting
No.
Input Type
Connect
ion
Measurement Range
Setting Range
Designated
Resolution
00
K
Thermocouple
TC
-210°C–1382°C
-200°C–1372°C
1°C/0.1°C
-199.9°C–999.9°C
-199.9°C–999.9°C
01
J
Thermocouple
TC
-210°C–860°C
-200°C–850°C
1°C/0.1°C
-199.9°C–860.0°C
-199.9°C–850.0°C
02
R
Thermocouple
TC -10°C–1710°C 0°C–1700°C 1°C
03
T
Thermocouple
TC
-210°C–410°C
-200°C–400°C
1°C/0.1°C
-199.9°C–410.0°C
-199.9°C–400.0°C
04
N
Thermocouple
TC
-210°C–1310°C
-199.9°C–999.9°C
-200°C–1300°C
-199.9°C–999.9°C
1°C/0.1°C
05
S
Thermocouple
TC -10°C–1710°C 0°C–1700°C 1°C
06
B
Thermocouple
TC -20°C–1802°C 0°C–1800°C 1°C
10
Pt100 RTD
-200°C–530°C
-200°C–500°C
1°C/0.1°C
-199.9°C–530.0°C
-199.9°C–500.0°C
11
JPt100 RTD
-200°C–520°C
-200°C–500°C
1°C/0.1°C
-199.9°C–520.0°C
-199.9°C–500.0°C