EasyManua.ls Logo

TOHO TTM-i4N - Control Mode Interlock Function; EV1 Alarm Function 2 Setting;Ev2 Alarm Function 2 Setting

TOHO TTM-i4N
74 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
59
・Control Mode Interlock Function
Interlock Function: It sets the control mode that will run the event function under the control mode interlock function.
Combinations with the standby sequence are the following:
1) No Event occurred
Event will not occur even when RUN/READY is switched.
2) Standby mode
Event will not occur even when RUN/READY is switched.
3) Event will occur (after temporarily leaving from the standby mode)
If the mode is switched from RUN to READY, Event will be turned OFF and returns to 2) Standby mode
■EV1 alarm function 2 setting/EV2 alarm function 2 setting
Character
Name
Description
Initial Value
1
SET4
AL1
SET5
AL2
Setting Mode Selection
Screen
Event 1 Output Parameter
Mode
Event 2 Output Parameter
Mode
※ Set5 will not be displayed
unless the control type is set
Settings about Event 1 Output Function
Settings about Event 2 Output Function
7
A1F2
A2F2
EV1 alarm function 2
setting
EV2 alarm function 2
setting
(PV Abnormality)
Event Function
**0
No Function
**1
PV Abnormality
Additional Function
*0*
None
*1*
Keep
*2*
Delay
*3*
Keep+Delay
Control Mode Interlock Function
0**
All modes
1**
RUN/MAN mode only
2**
RUN mode only
000
Event Function (PV Abnormality) is a function that outputs the signal (ON/OFF) from the output that was assigned to Event
Function Setting 2 when the input abnormality is detected. It is valid when Event Function Setting 2 is set to **1.
It can start or stop event and other system in case of the wrong setting of the input type or wrong wiring of input,
disconnection, and short circuit.
Operation of Additional Function and Control Mode Interlock Function is the same asthat of Event Function Setting 1.
Sample Setting of PV Abnormality: Set “001” for PV Abnormality = ON, Additional Function = OFF, and Control Mode =
Interlock All Mode.