■ Sensitivity setting for OUT1
Character
Name
Description
Initial Value
1
SET3
CNT
Setting Mode Selection
Screen
Control Parameter Mode
Settings about Control
19
C1
Sensitivity setting for
OUT1
Setting Range: 0–999 or 0.0–999.9
Setting Unit: °C or °F
1
Sets the sensitivity (hysteresis) of the ON/OFF action of output 1. In case of the heating control, the sensitivity will be placed
below SV.
■ OFF point position setting for OUT1
Character
Name
Description
Initial Value
1
SET3
CNT
Setting Mode Selection
Screen
Control Parameter Mode
Settings about Control
20
CP1
OFF point position
setting for OUT1
Setting Range: -199–999 or -199.9–999.9
Setting Unit: °C or °F
0
Moves the OFF point of the sensitivity of output 1. The entire range of sensitivity will be moved.
Sets the position of OFF point (offset for SV) for the ON/OFF operation of reverse action.