26
■ Setting of PV Filter
Character
Name
Description
Initial Value
1
SET1
INP
Setting Mode Selection
Screen
Input Parameter Mode
Settings about Input
5
PDF
Setting of Input Filter
Setting Range: 0.0–99.9
Setting Unit: Second
00
[Function]
A function to programmatically realize CR filtering effect by performing a primary delay operation for PV of the input.
Filter effect will be set through time constant.
(Time constant is a time that was spent before PV to reach up to approximately 60% when the input has changed in a
step-by-step manner)
※The purposes of PV filter are the following:
① The effect of the electrical noise that was applied to the input can be minimized by eliminating the high-frequency
noise.
② The response against sudden change of the input can be delayed.