42 model 3000 ADMAP-5M AN712 Module User’s Manual
Chapter 5 Application Interface
5
A list of accessible information on MMS command messages and response messages
and message types is shown in Table 5-1.
The meanings of the functions and parameters for each message are described in the
following pages.
Table 5-1 Information Accessible by TOSDIC-CIE 6000/5000 System
Item Header Description
Tag information table
read
MMS RC/MMS RR Tag parameter read by specifying a terminal
unit (PCS, DPCS, SIF5300, TIF)
Tag information write (W) MMS WC/MMS WR Tag information write in word (W) units (PCS,
DPCS, SIF5300, TIF)
Tag information write (B) MMS WC/MMS WR Tag information write in bit (B) units (PCS,
DPCS, SIF5300, TIF)
Tag information write (D) MMS WC/MMS WR Tag information write in double word (D) units
(PCS, DPCS, SIF5300, TIF)
PCS parameter read MMS RC/MMS RR PCS parameters read: XPR, XPW, XPF, XPT,
XTS, XTR, XTH, XTU, XCP, XCS, XCM, FMT,
STL
PCS parameter (W) write MMS WC/MMS WR PCS parameters (XPW, XTS, etc.) write in
word units
PCS parameter (B) write MMS WC/MMS WR PCS parameters (XPW, XTS, etc.) write in bit
units
PCS parameter (D) write MMS WC/MMS WR PCS parameter (XPR) write in double word
units
Polynomial line table
read
MMS RC/MMS RR Polynomial line table number data read (PCS,
DPCS)
Polynomial line table
write
MMS WC/MMS WR Polynomial line table number write (PCS,
DPCS)
Station SYS information
details
MMS RC/MMS RR PCS detailed station SYS information read
(serial bus, parallel bus)
Calendar setting MMS IC/MMS IR Date and time correction
DPCS parameter read MMS RC/MMS RR DPCS parameter read
DPCS parameter write MMS WC/MMS WR DPCS parameter write
OIS parameter read MMS RC/MMS RR OIS parameter read
OIS parameter write MMS WC/MMS WR OIS parameter write
MV value write (%MV) MMS WC/MMS WR MV (%MV) value write in controller
MV value write (∆MV) MMS WC/MMS WR MV (∆MV) value write in controller