6F8C1048 85
6.2Dual Line System
6
(4) S3 down or downgrade to standby
If the S is judged irrecoverable by its own diagnostic function, the S3 forces itself down. 
The AN712 detects it with the healthy counter and S3 operation monitor function, and 
stops scan transmission.
When the S is downgraded to standby status, it is also detected by the S3 operation 
monitor function and scan transmission is stopped.
6.2.2 Standby operation
(1) Initializing
When initial start sets the system in standby status, no operation is needed by the S3 
application. As the switch AO is set to the ON position, the system is automatically 
engaged in the ADMAP transmission lines and operates online.
(2) Upgrading to online
The application operation concerning the AN712 module upgraded from standby to 
online operation is the same as the initializing operation shown in figure 6-2. However, it 
is not necessary to issue an inring request or an online request because the switch AO is 
set to the ON position.