6F8C1048 79
5.9AN712 Module Management and Control
5
5.9.4 Scan transmission start/stop
<Function>
To instruct a specified AN712 module to start or stop scan transmission
<Message format>
<Response status>
Refer to section 5.9.1.
 
15                                  0 
+00(0x00)
+16(0x10)
+20(0x14)
SS
Scan registration request  (0xC007) 
Request status  (0x0) 
Command 
Response 
15                                  0 
+00(0x00)
+16(0x10)
Same as request 
Scan registration response  (0xC087)
Response status  (error code) 
SH SM SL 
SS: Scan transmission stat (1)/stop  (0) 
SH: High  (1), SM: Medium  (1), SL: Low speed 
Byte address 
+18
0x12
'AN712 SMG RQ    ' 
'AN712 SMG RR    ' 
+18(0x12)
+20(0x14)
Auxiliary information  (0x0) 
Auxiliary information  (0x0) 
+14(0x0E)
+14(0x0E)