184 GX9 ASD Installation and Operation Manual
Motor Overload Protection Level 1
Program Fundamental Motor Set 1
This parameter specifies the motor overload current level for Motor Set 1. This
value is entered as either a percentage of the full load rating of the ASD or as a
percentage of the FLA of the motor.
The unit of measurement for this parameter may be set to A/V (Amps) or it may
be set as a percentage of the ASD rating. The nameplated FLA of the motor
may be entered directly when Amps is selected as the unit of measurement (see
F701 to change the display unit).
Motor Overload Protection Level 1 settings will be displayed in Amps if the
EOI display units are set to A/V rather than %.
Direct Access Number — F600
Parameter Type — Numerical
Factory Default — 100.00
Changeable During Run — Yes
Minimum — 10.00 (A)
Maximum — 100.00 (A)
Units — V or % (F701)
Stall Prevention Level
Program Protection Stall
This parameter specifies the output current level at which the output frequency
is reduced in an attempt to prevent an over-current trip. The over-current level
is entered as a percentage of the maximum rating of the ASD.
Note: The Motor Overload Protection parameter must enabled at F017
to use this feature.
Direct Access Number — F601
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200
Units — %
ASD Trip Record Retention Selection
Program Protection Trip Settings
This parameter Enables/Disables the Trip Record Retention setting. When
enabled, this feature logs the trip event and retains the trip information when the
system powers down. The trip information may be viewed from the (Program
Utilities Trip History screen or the Monitor screen.
When disabled, the trip information will be cleared when the system powers
down.
Settings:
0 — Cleared after Power Off
1 — Hold after Power Off
Direct Access Number — F602
Parameter Type — Selection List
Factory Default — Cleared after Power
Off
Changeable During Run — No
F600 F602