32RCA001TS-02ISEN
11
RBP-RC001-E Installation & Owner's Manual
Connection to External Equipment
Example of connection to external equipments
Name I/O Item
This unit side Equipment side
I/O conditions Circuit
Terminal
name
Circuit example I/O conditions
Digital I/O
terminal
Signal
output
Contact A static signal
output
Contact permissible
voltage/current
DC 24 V/90 mA
Signal
input
Contact A static or
pulse signal input
(It depends on the
input function settings.
For details, Refer to
the I/O function list (P.
50).)
A contact that supports
microcurrent must be
selected and used.
Pulse width of
pulse signal
input: 500 ms or
more
* Wire the cables so that the user does not touch the power supply directly.
* On the equipment side, use a basically insulated power circuit and place it in a location that where the user cannot touch it.
* Procure the external power supply for the digital I/O locally.
* Functions can be assigned to digital inputs 1 to 3 and digital outputs 1 to 2. Refer to “I/O settings (P. 40)”
* Group remote controller cannot be connected to equipment by our remote monitoring or open protocol (BACnet, Modbus).
[REQUIREMENT]
• Fasten the screws to the terminal block with torque of 0.5 N
·
m.
DC
12V or 24V
+
-
DO2
DO1
DI3
DI2
DI1
COM
+VS
G
B
A
Input / output
Input / output
Output 2
Output 1
Input 3
Input 2
Input 1
Signal
Signal
External
power
supply
input
Digital
input
+VS
External
power
supply
DO1
DO2
DI1
DI2
DI3
COM