DN code list
DN code Item Description
Initial
value
Restart
005
Static or pulse
operation signal
Switches operation input to pulse signal input.
0: Static signal
1: Pulse signal
0
Not
neces-
sary
006 Reset failure outage
Enable fault reset when GR is externally stopped.
If it is disabled, a failure is retained during external stop.
0: Disabled
1: Enabled
0
Not
neces-
sary
007
Level of operating
output
Switches the operations of the operation lamp and the operating output.
0: Output during GR operation.
1: Output during GR operation and system operation (system individual
operation).
2: Output during GR operation, system operation (system individual
operation), and MC operation (including unit/external operation).
1
Not
neces-
sary
008 Level of failure output
Switches the operations of the failure lamp and the failure output.
0: Output in the event of a GR failure.
1: Output in the event of a GR failure and a system failure.
2: Output in the event of a GR failure, system failure, and MC failure
(including unit/external operation).
1
Not
neces-
sary
009
Demand control
display
Displays demand control on the GR operation screen.
0: Non-display
1: Display
0
Not
neces-
sary
00A Power failure recovery
Enables the auto recovery function when power is restored.
Regardless of the power failure time, restores the operating state of the
remote controller and the system individual Run/Stop states to the states
before the power failure when power is restored.
0: Disabled
1: Enabled
[CAUTION]
If the GR uses Run/Stop input (static signal) externally, the GR follows the
Run/Stop input signals.
0
Not
neces-
sary
00B
Pwr failure recovery
time (s)
Sets the time for power failure recovery.
If the power failure is within the set time, the remote controller Run/Stop
and system individual Run/Stop states are restored to the state before the
power failure when power is restored.
To enable the code, set a time of 3 seconds or more.
0 seconds to 2 seconds: Disabled
3 seconds to 9 minutes and 59 seconds: Enabled
[CAUTION]
• If power failure recovery (DN code: 00A) is enabled, power failure
recovery is given priority.
• Detection of a power failure time may have an error of up to 2 seconds.
Consider the error when setting the power failure recovery time.
• If the GR uses Run/Stop input (static signal) externally, the GR follows
the Run/Stop input signals.
0
Not
neces-
sary
00C
Pwr Failure recovery
time (m)
0
Not
neces-
sary
00D
Pwr failure recovery
when MC remote
Enables power failure recovery when a remote MC is operating.
If it is enabled, and it can be checked within 10 seconds after power is
restored that a remote MC is operating, operation is restored regardless of
the state before the power failure, avoiding the stop of the MC.
0: Disabled
1: Enabled
[CAUTION]
If the GR uses Run/Stop input (static signal) externally, the GR follows the
Run/Stop input signals.
0
Not
neces-
sary
012
Invalid GR demand
with ext MC ctrl
Makes GR demand with external MC control invalid.
If it is valid, the MC makes demand with the demand signal of the GR even
if the MC is set to Unit or External.
0: Enabled
1: Disabled
0
Not
neces-
sary