Operation Settings
Set the operation conditions for each GR system.
List of “Operation Settings” setting items
Item Description
MC Gr.Ctrl Set MC group control to ON/OFF.
MC Gr.Ctrl OFF: Operate all MCs in the same system.
MC Gr.Ctrl ON: Control the number of MCs to operate in the same system according to load.
Operation procedure:
Use [Λ], [V], [<], and [>] to select the system to change and press [●] (Confirm) to switch between ON and
OFF.
Mode Switch the mode between Stop, Cool, and Heat.
Operation procedure:
Use [Λ], [V], [<], and [>] to select the system to change and press [●] (Confirm) to switch between Stop, Cool,
and Heat.
Cool PST
Heat PST
Set the set temperatures for Cool/Heat.
Operation procedure:
1 Use [Λ], [V], [<], and [>] to select the system to change and press [●] (Confirm) to display the set
temperature input screen.
2 Use [<] and [>] to select an input digit, use [Λ] and [V] to change the value, and press [●] (Confirm).
The valid setting ranges are as in the table below.
Model
Cool PST [°C] Heat PST [°C]
Initial
value
Setting range
Initial
value
Setting range
USX, EDGE Series 7.0 4.0 to 30.0 45.0 25.0 to 55.0
SFMC Series 4, 5 7.0 5.0 to 25.0 45.0 35.0 to 55.0
CAONS700
65.0 50.0 to 90.0
Heat Recovery CAONS
Series 1
– – 65.0 50.0 to 85.0
Heat Recovery CAONS
Series 2
30.0 9.0 to 35.0 65.0 50.0 to 85.0
Demand Set the demand current (for SFMC Series 4, 5, demand capacity).
Operation procedure:
1 Use [Λ], [V], [<], and [>] to select the system to change and press [●] (Confirm) to display the value input
screen.
2 Use [<] and [>] to select an input digit, use [Λ] and [V] to change the value, and press [●] (Confirm).
The range of values that can be input is “0” to “30000”.
*
The initial value is “0”. Note that if you enable demand/power saving with an incorrect setting, the unit will be
stopped.
Operation settings screen Set temperature input screen
Demand value input screen