6.12.2 Regenerative power ride-through control (Deceleration
stop)
 : Regenerative power ride-through control (Deceleration stop)
Function
1) Regenerative power ride-through control:
When momentary power failure occurs during operation, this function makes operation continue
using the regeneration energy from a motor.
2) Deceleration stop during power failure:
When momentary power failure occurs during operation, this function stops the motor quickly and
compulsorily using the regeneration energy from the motor.
Deceleration time varies according to load.
When deceleration stop during power failure is operated, the message “” displays on the
operation panel.
After the forced stop, the inverter remains static until you put off the operation command
momentarily.
[Parameter setting]
Title Function Adjustment range Default setting
f302
Regenerative power ride-through
control (Deceleration stop)
0: Disabled
1: Regenerative power ride-through control
2: Deceleration stop during power failure
0
Note 2: Even if these functions are used, a motor may coast according to load conditions.
In this case, use the auto-restart function (f301) for the smooth restart after power supply is restored .
An example of setting when f302=1
[When power is interrupted]
Note 4: If power is interrupted during deceleration stop, power ride-through control will not be performed.
The time for which the operation of the motor
can be continued depends on the machine
inertia and load conditions. Before using this
function, therefore, perform verification tests.
Use with the retry function allows the motor to
be restarted automatically without being
brought to an abnormal stop.
Motor speed
About 100ms~10s
Input voltage
Coasting stop
DC Voltage
Regenerative power
ride-through control selection

Table of Contents

Other manuals for Toshiba TOSVERT VF-nC3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-nC3 and is the answer not in the manual?

Toshiba TOSVERT VF-nC3 Specifications

General IconGeneral
ModelVF-nC3
CategoryInverter
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, sensorless vector control
Overload Capacity150% for 60 seconds
Input Frequency50/60 Hz
Enclosure RatingIP20
Input Voltage200-240V AC
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
Ambient Temperature-10°C to +50°C
CommunicationModbus RTU
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Braking UnitBuilt-in braking transistor (for models up to 22kW), External braking resistor required

Related product manuals