[If momentary power failure occurs]
An example of setting when f302=2
• Even after the recovery from an input power failure, the motor continues deceleration stop. If the DC voltage falls
below a certain level, however, control will be stopped and the motor will coast.
• If the voltage in main circuit falls below main circuit undervoltage (moff) level at operation deceleration stop
during power failure, the motor will coast and inverter displays stop and 0.0 alternately. The motor continues
coasting even after power supply is restored.
Motor speed
In
p
ut volta
g
e
Note 5: If momentary power failure occurs during deceleration stop,
power ride-through control will not be performed.
DC Voltage
Normal acceleration
Motor speed
Time
Input voltage
Deceleration stop

Table of Contents

Other manuals for Toshiba TOSVERT VF-nC3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-nC3 and is the answer not in the manual?

Toshiba TOSVERT VF-nC3 Specifications

General IconGeneral
ModelVF-nC3
CategoryInverter
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, sensorless vector control
Overload Capacity150% for 60 seconds
Input Frequency50/60 Hz
Enclosure RatingIP20
Input Voltage200-240V AC
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
Ambient Temperature-10°C to +50°C
CommunicationModbus RTU
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Braking UnitBuilt-in braking transistor (for models up to 22kW), External braking resistor required