E6581595
F-61
6
6.18.7 Cancel the operation command
f719 : Selection of operation command clear
Function
This parameter allows you to select operation command retained or operation command canceled,
when coast stop occurs due to standby terminal function (ST) or coast stop command terminal
function(FRR), and when under voltage in main circuit alarm() occurs, during panel operation or
RS485 communication operation.
Parameter setting At coast stop
At under voltage in main circuit alarm()

Operation command canceled Operation command retained

Operation command retained

Operation command canceled
Operation command retained :
Inverter restarts due to canceling coast stop at coast stop.
Inverter restarts due to supply power source again when the under voltage in main circuit alarm ()
occurs.
Operation command canceled :
Inverter doesn’t restart after coast stop or occurring the under voltage in main circuit alarm ().
Press RUN key to operate again in panel operation.
Switch to ON the operation command in RS485 communication operation.
Title Function Adjustment range Default setting
f719
Selection of operation
command clear
0: Clear at coast stop and retained at
moff.
1: Retained at coast stop and moff.
2: Clear at coast stop and moff.
1
[Setup example of input terminal]
When it is assigned to the S1 terminal.
Title Function Adjustment range Setting
f113
Input terminal selection 3A
(S1)
0-201 6: ST (Standby)
f113
Input terminal selection 3A
(S1)
0-201 96: FRR (Coast stop command)
Setting value 7, 97 are reverse signa
6.18.8 Parameter registration to easy setting mode
 -  : Easy setting mode parameter 1 to 24
Up to 24 arbitrary parameters can be registered to easy setting mode. Refer to section 4.5 for details.

Table of Contents

Other manuals for Toshiba TOSVERT VF-nC3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-nC3 and is the answer not in the manual?

Toshiba TOSVERT VF-nC3 Specifications

General IconGeneral
ModelVF-nC3
CategoryInverter
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, sensorless vector control
Overload Capacity150% for 60 seconds
Input Frequency50/60 Hz
Enclosure RatingIP20
Input Voltage200-240V AC
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
Ambient Temperature-10°C to +50°C
CommunicationModbus RTU
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Braking UnitBuilt-in braking transistor (for models up to 22kW), External braking resistor required

Related product manuals