E6581595
C-15
3
[Example of how to adjustment the FM terminal frequency meter]
* Use the meter's adjustment screw to pre-adjust zero-point.
Operation panel action LED display Operation
- .
Displays the output frequency.
(When standard monitor display selection = [Output frequency])

The first basic parameter ” (history function) is displayed.

Turn the setting dial to select .
.
Output frequency can be read by pressing the center of the setting
dial.
.
Turn the setting dial to adjust the meter.
Note that the meter's indicator changes at this time, but the inverter's
display (monitor) does not change.


Press the center of the setting dial to save the meter's calibrations.
 and the frequency are displayed alternately.
+
.
The display returns to its original indications.
(When standard monitor display selection = [Output frequency])
Adjusting the meter in inverter stop state
Adjustment of output current (=1)
If, when adjusting the meter for output current, there are large fluctuations in data during adjustment,
making adjustment difficult, the meter can be adjusted in inverter stop state.
When setting  to  for fixed output 1 (output current 100% equivalent), a signal of absolute
values will be output (inverter's rated current = 100%). In this state, adjust the meter with the  (Meter
adjustment) parameter.
Similarly, if you set  to  for fixed output 2 (output current 50% equivalent), a signal that is sent
out when half the inverter's rated current is flowing will be output through the FM terminal.
After meter adjustment is ended, set  to (output current).
Other adjustments ( = , - , , , )
 = : When fixed output 3 (other than the output current) is set, a signal of the the value for
other monitors is fixed at the following values and output through the FM terminal.
100% standard value for each item is the following:
=0, 2, 12 : Maximum frequency (h)
=3, 4 : 1.5 times of rated voltage
=13 : Maximum input value (5V, 10V, or 20mA)
=18 : Maximum value (1000)
MODE
MODE
MODE

Table of Contents

Other manuals for Toshiba TOSVERT VF-nC3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-nC3 and is the answer not in the manual?

Toshiba TOSVERT VF-nC3 Specifications

General IconGeneral
ModelVF-nC3
CategoryInverter
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, sensorless vector control
Overload Capacity150% for 60 seconds
Input Frequency50/60 Hz
Enclosure RatingIP20
Input Voltage200-240V AC
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
Ambient Temperature-10°C to +50°C
CommunicationModbus RTU
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Braking UnitBuilt-in braking transistor (for models up to 22kW), External braking resistor required

Related product manuals