4.3.2 Return to default settings
 : Default setting
Function
It is possible to return groups of parameters to their defaults, clear run times, and record/recall set
parameters.
[Parameter setting]
Title Function Adjustment range Default setting

Default setting
0: -
1: 50Hz default setting
2: 60Hz default setting
3: Default setting 1 (Initialization)
4: Trip record clear
5: Cumulative operation time clear
6: Initialization of type information
7: Save user setting parameters
8. Load user setting parameters
9. Cumulative fan operation time
record clears
10 to 12: -
13: Default setting 2 (complete
initialization)
0
This function will be displayed as 0 during reading on the right. This previous setting is displayed on the left.
Example:
 cannot be set during the inverter operating. Always stop the inverter first and then program.
Programmed value
50 Hz default setting (=)
Setting  to sets the following parameters for base frequency 50 Hz use.
(The setting values of other parameters are not changed.)
Max. frequency () 50Hz Upper limit frequency () 50Hz
Base frequency 1 () 50Hz Base frequency 2 () 50Hz
VI input point 2 frequency () 50Hz Motor rated RPM () 1410 min
-1
60 Hz default setting (=)
Setting  to sets the following parameters for base frequency 60 Hz use.
(The setting values of other parameters are not changed.)
Max. frequency () 60Hz Upper limit frequency () 60Hz
Base frequency 1 () 60Hz Base frequency 2 () 60Hz
VI input point 2 frequency () 60Hz Motor rated RPM () 1710 min
-1

Table of Contents

Other manuals for Toshiba TOSVERT VF-nC3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-nC3 and is the answer not in the manual?

Toshiba TOSVERT VF-nC3 Specifications

General IconGeneral
ModelVF-nC3
CategoryInverter
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, sensorless vector control
Overload Capacity150% for 60 seconds
Input Frequency50/60 Hz
Enclosure RatingIP20
Input Voltage200-240V AC
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat, Short Circuit
Ambient Temperature-10°C to +50°C
CommunicationModbus RTU
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Storage Temperature-20°C to +60°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Braking UnitBuilt-in braking transistor (for models up to 22kW), External braking resistor required