124
TK 61753-2-MM-EN
wire terminals, or install a new connector and wire terminals. Refer to the appropriate Parts Manual for the correct
connector and terminal part numbers.
2. Place a new copper sealing washer on the high pressure cutout switch.
3. Install the high pressure cutout switch and torque it to 27 ± 3 N•m (20 ± 2 ft-lb).
4. Connect the wires.
5. Pressurize the compressor and test for leaks.
6. If no leaks are found, open the refrigeration service valves and place the unit in operation.
High Pressure Relief Valve
Removal
1. Recover the refrigerant charge.
2. Unscrew and remove the high pressure relief valve.
Installation
1. Apply a refrigerant oil to the O-ring of the high pressure relief valve.
2. Install and tighten the high pressure relief valve.
3. Pressurize the refrigeration system and test for leaks. If no leaks are found, evacuate the system.
4. Recharge the unit with the proper refrigerant and check the compressor oil level.
Discharge Pressure Transducer
Removal
1. Recover the refrigerant charge.
2. Disconnect the wires and remove the discharge pressure transducer.
Installation
1. Apply a refrigerant Loctite to the threads of the discharge pressure transducer.
2. Install and tighten the discharge pressure transducer and reconnect the wires.
3. Pressurize the refrigeration system and test for leaks. If no leaks are found, evacuate the system.
4. Recharge the unit with the proper refrigerant and check the compressor oil.
Suction Pressure Transducer
Removal
1. Pump down the low side and equalize pressure to slightly positive.
2. Disconnect the wires and remove the suction pressure transducer.
Installation
1. Apply a refrigerant Loctite to the threads of the suction pressure transducer.
2. Install and tighten the suction pressure transducer and reconnect the wires.
3. Pressurize the low side and check for leaks. If no leaks are found, evacuate the low side.
4. Open the refrigeration valves and place the unit in operation.
Electronic Throttling Valve (ETV)
Removal
1. Pump down the low side and equalize the pressure to slightly positive.
RReeffrriiggeerraattiioonn SSeerrvviiccee OOppeerraattiioonnss