Dry mortarless installation with installation kit TQ in wooden beam / laminated beam ceiling, suspended
Fig. 103: Dry mortarless installation with installation kit TQ into wooden beam / laminated beam ceiling, suspended
(illustration representative, alternative ceiling construction possible on request)
1 FKR-EU
2.11 Installation kit TQ (factory assembled)
5.1 Dry wall screw
6.5 Mineral wool filling depending on ceiling con-
struction
7.11 Trim panel, same construction as 7.19
7.15 Wood sheet, min. 600 kg/m³
7.16 Wooden beam / gluelam min. 100 × 80 mm
(reduce distances between wooden beams to the
size of the installation opening)
7.17 Trimmers, wooden beam / glued laminated
timber min. 100 × 80 mm
7.19 Fire-resistant cladding (ceiling-dependent)
Z Spigot construction 370 mm
Flange construction 342 mm
Up to EI 90 S
Up to EI 60 S
EI 30 S
Additional requirements: dry mortarless installation
with installation kit TQ into wooden beam / lami-
nated beam ceilings
Wooden beam ceiling,
Ä
on page 36
Installation kit TQ,
Ä
on page 32
≥ 75 mm distance from the fire damper to load-
bearing structural elements (structure 100 mm)
≥ 200 mm distance between two fire dampers in
separate installation openings
Fasten the cover plate to the wooden beam / glue-
laminated beam ceiling with 4 (for nominal widths up
to 400 mm) or 12 (for nominal widths from 450 mm)
dry wall screws Æ ≥ 4.2 mm
Note:
Structural and fire resistance properties of the ceiling
construction, including the attachment to the con-
crete or any required reinforcement, have to be eval-
uated and ensured by others.
Installation
Wooden beam ceilings > Dry mortarless installation with installation ...