5.6.5 Dry mortarless installation without installation kit
Fig. 45: Dry mortarless installation into a lightweight partition wall, without installation kit
1 FKR-EU
2.19 Joint filler (ready-to-use putty or equivalent)
3.2 Lightweight partition wall with metal support
structure, cladding on both sides
6.5 Mineral wool (depending on wall construction)
7.13 Cladding
–
Up to EI 60 S
B Operating side
Additional requirements: dry mortarless installation
into lightweight partition walls without installation
kit
Lightweight partition wall,
Ä
on page 34
≥200 mm distance between two fire dampers
≥ 75 mm distance from fire damper to load-bearing
structural elements
1. Create a circular installation opening with nominal
width +20 mm.
2. Chamfer the outer layer of the cladding all round
on both sides and completely close off the sur-
rounding gap on both sides with joint filler to the
depth of the cladding.
Installation
Lightweight partition walls > Dry mortarless installation without installati...