Parameterizing and Configuring
Configuring the devices at EtherNet/IP
128
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
n Input data – TBEN-S1-4DXP [}44]
status word + 8 words
Word no. Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Status
0x0000 - FCE - - - COM V1 - - - - - - - ARGEE Diag
Warn
IN
0x0001 - - - - - - - - - - - - DX3
C3P4
DX2
C2P4
DX1
C1P4
DX0
C0P4
Diagn.
0x0002 - - - - ERR3 ERR2 ERR1 ERR0 - - - - - - VERR V2
Ch4-7
VERR V1
Ch0-3
Latch IN
0x0003 - - - - - - - - - - - - DX3 DX2 DX1 DX0
CNT Ch0
0x0004 Counter value LSB
0x0005 Counter value MSB
Freq. Ch0
0x0006 Frequency MSB Frequency LSB
Module
status
0x0007 -
PWM
diag. Ch 3
0x0008 - - - - - - - - - - - - - - PWM OUT ERR
DO3
n Output data – TBEN-S1-4DXP [}53]
control word + 4 words
Word no. Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Control
0x0000
OUT
- - - - - - - - - - - - - - - -
0x0001 - - - - - - - - - - - - DX3
C3P4
DX2
C2P4
DX1
C1P4
DX0
C0P4
Latch
reset
0x0002 - - - - - - - - - - - - DX3 DX2 DX1 DX0
CNT-
reset
0x0003 - - - - - - - - - - - - - - - CNT
reset
PWM Ch3
0x0004 - - - - - - - - Duty Cycle

Table of Contents