Attribute no. Designation Get/Set Type Meaning
Dec. Hex.
12 0x0C Data
representation
G/S USINT 0: Standard
1: NE43
2: Extended range
13 0x0D Temperature
unit
G/S USINT 0: Celsius
1: Fahrenheit
14 0x0E Input averaging
filter DIFT
G/S USINT 0 = standard
1 = smooth
2 = fast
3: off
15 0x0F Deactivate
channel
G/S USINT 0 = no
1 = yes
16 0x10 Deactivate
diagnostics
G/S USINT 0 = no
1 = yes
17 0x11 Mains suppres-
sion
G/S USINT 0: off
1: 50 Hz
2: 60 Hz
18 0x12 Upper limit
value
exceeded
G USINT 0: -
1: active
19 0x13 Lower limit value
underrun
G USINT 0: -
1: active
20 0x14 Overflow G USINT 0: -
1: active
21 0x15 Underflow G USINT 0: -
1: active
22 0x16 Cold junction
error
G USINT 0: -
1: active
23 0x17 Overcurrent
(RTD only)
G USINT 0: -
1: active
24 0x18 Wire break G USINT 0: -
1: active
25 0x19 Overcurrent
supply VAUX1
G USINT 0: -
1: active
26 0x1A Input value G UINT