parameters vacon • 57
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
8.8 Digital outputs (Control panel: Menu PAR -> P8)
8.9 Analogue outputs (Control panel: Menu PAR -> P9)
Code Parameter Min Max Unit Default ID Selections
P8.1
RO1 signal
selection
0 11 2 313
0 = Not used
1 = Ready
2 = Run
3 = Fault
4 = Fault Inverted
5 = Warning
6 = Reversed
7 = At Speed
8 = Motor regulator active
9 = FB Control Word.B13
10 = FB Control Word.B14
11 = FB Control Word.B15
P8.2
RO2 signal sel-
cetion
0 11 3 314 As parameter 8.1
P8.3
DO1 signal sel-
cetion
0 11 1 312 As parameter 8.1
P8.4 RO2 inversion 0 1 0 489
0 = No inversion
1 = Inverted
Table 8.8: Digital outputs
Code Parameter Min Max Unit Default ID Selections
P9.1
Analog output
signal selection
0 4 1 307
0 = Not used
1 = Output freq. (0-f
max
)
2 = Output current (0-I
nMotor
)
3 = Motor torque (0-T
nMotor
)
4 = PI output (0 - 100%)
P9.2
Analog output
minimum
0 1 0 310
0 = 0 mA
1 = 4 mA
Table 8.9: Analogue outputs