parameters vacon 53
24-hour support +358 (0)40 837 1150 • Email: vacon@vacon.com
8
NOTE! These parameters are shown, when P17.2 = 0.
8.3
Table 8.3: Start / stop setup
Code Parameter Min Max Unit Default ID Note
i
i
i
i
i
P2.1
Remote Control
Place 1 Selection
0
1 0 172
0 = I / O terminals
1 = Fieldbus
P2.2
Start function
0
1 0 505
0 = Ramp
1 = Flying start
P2.3
Stop function
0
1 0 506
0 = Coasting
1 = Ramp
P2.
4
I
/ O Start / Stop
logic
0 3 2 300
I / O control I / O control
signal 1 signal 2
0 F
orward Backward
1 Fwd(edge) Inverted Stop
2 Fwd(edge) Bwd(edge)
3 Start Reverse
P2.
5 Lo
cal / Remote 0 1 0 211
0 =
Remote control
1 = Local control
P2.6
Ke
ypad control
dir
ectio
n
0 1 0 123
0 =
Forward
1 = Backward
Start / stop setup (Control panel: Menu PAR -> P2)
Motor identifica-
tion
01 0631
0 = Not active
1 = Standstill identification
(need run command within
20 s to activate)
Rs voltage drop 0,00 100,00 % 0,00 675
Voltage drop over motor
windings as % of U
nmot
at
nominal current.
Overvoltage con-
troller
02 1607
0 = Disabled
1 = Enabled, Standard
mode
2 = Enabled, Shock load
mode
Undervoltage
controller
01 1608
0 = Disable
1 = Enable
Code Parameter Min Max Unit Default ID Note
Table 8.2: Motor settings
i
P1.18
P1.19
P1.20
P1.21