parameter descriptions vacon 65
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
1.15 TORQUE BOOST
When this parameter has been activated, the voltage to the motor changes au-
tomatically with high load torque which makes the motor produce sufficient
torque to start and run at low frequencies. The voltage increase depends on
the motor type and power. Automatic torque boost can be used in applications
with high load torque, e.g. in conveyors.
0 = Disabled
1 = Enabled
Note: In high torque - low speed applications - it is likely that the motor will
overheat. If the motor has to run a prolonged time under these conditions,
special attention must be paid to cooling the motor. Use external cooling for
the motor if the temperature tends to rise too high.
Note: The best performance can be reached by running motor identification,
see par. 1.18.
1.16 SWITCHING FREQUENCY
Motor noise can be minimised using a high switching frequency. Increasing
the switching frequency reduces the capacity of the frequency converter unit.
Switching frequency for Vacon 10: 1.5…16 kHz.
1.17 BRAKE CHOPPER
Note! An internal brake chopper is installed in three phase supply MI2 and MI3
size drives.
0 = Disable (No brake chopper used)
1 = Enable: Always (Used in Run and Stop state)
2 = Enable: Run state (Brake chopper used in Run state)
When the frequency converter is decelerating the motor, the energy stored to the in-
ertia of the motor and the load are fed into an external brake resistor, if the brake
chopper has been activated. This enables the frequency converter to decelerate the
load with a torque equal to that of acceleration (provided that the correct brake re-
sistor has been selected). See separate Brake resistor installation manual.
1.18 MOTOR IDENTIFICATION
0 = Not active
1 = Standstill identification
When Standstill identification is selected, the drive will perform an ID-run
when it is started from selected control place. Drive has to be started within
20 seconds, otherwise identification is aborted.