parameter descriptions vacon • 81
24-hour support +358 (0) 201 212 575 • Email: vacon@vacon.com
9
9.7 Digital outputs (Control panel: Menu PAR -> P8)
8.1 RO1 SIGNAL SELECTION
8.2 RO2 SIGNAL SELCETION
8.3 DO1 SIGNAL SELCETION
Table 9.2: Output signals via RO1, RO2 and DO1
Setting Signal content
0 = Not used
Output is not in operation.
1 = Ready The frequency converter is ready to operate.
2 = Run
The frequency converter operates (motor is running).
3 = Fault A fault trip has occurred.
4 = Fault inverted
A fault trip has not occurred.
5 = Warning A warning is active.
6 = Reversed
The r
everse command has been selected, output fre-
quency to the motor is negative.
7 = At speed The output frequency has reached the set reference.
8 = Motor regulator active
Each of motoring current regulator,generating current
reg. ,over voltage reg. ,under voltage reg. is active.
9 = FB Control Word.B13
Output can be controlled with B13 in the fieldbus control
word.
10 = FB Control Word.B14
Output can be controlled with B14 in the fieldbus control
word.
11 = FB Control Word.B15
Output can be controlled with B15 in the fieldbus control
word.