vacon • 17 Description of Groups
2
2.2.3 Group References: Menu PAR G3
Code Parameter Min Max Unit Default ID Level Description
P3.1 Minimum frequency 0.00 P3.2 Hz 0.00 101 Basic
Minimum allowed
frequency reference
P3.2 Maximum frequency P3.1 320.00 Hz 50.00 102 Basic
Maximum allowed
frequency reference
P3.3
AUTO
Frequency reference
selection
0
2
1)
2 1819 Basic
Selection of AUTO
reference source:
0 = Preset frequency
0
1 = Motor potentiom-
eter
2 = Non-ASi fieldbus
P3.4 Preset frequency 0 P3.1 P3.2 Hz 50.00 114 Basic Multistep speed 0
P3.5 Preset frequency 1 P3.1 P3.2 Hz 10.00 105 Basic
Multistep speed 1
2)
P3.6 Preset frequency 2 P3.1 P3.2 Hz 15.00 106 Basic
Multistep speed 2
2)
P3.7 Preset frequency 3 P3.1 P3.2 Hz 20.00 126 Basic
Multistep speed 3
2)
P3.8 Preset frequency 4 P3.1 P3.2 Hz 25.00 127 Advanced
Multistep speed 4
2)
P3.9 Preset frequency 5 P3.1 P3.2 Hz 30.00 128 Advanced
Multistep speed 5
2)
P3.10 Preset frequency 6 P3.1 P3.2 Hz 40.00 129 Advanced
Multistep speed 6
2)
P3.11 Preset frequency 7 P3.1 P3.2 Hz 50.00 130 Advanced
Multistep speed 7
2)
P3.12
Motor potentiometer
Mode
0 1 0 1860 Advanced
0: Step up/down
1: Continuous
P3.13
Motor potentiometer
Step Up
0.01 50.00 Hz 5.00 1862 Basic
At any edge of
increase signal
P3.14
Motor potentiometer
Step Down
0.01 50.00 Hz 5.00 1863 Basic
At any edge of
decrease signal
P3.15
Motor potentiometer in
Reverse
0 1 0 1898 Basic
0: Forward
1: Reverse
P3.16
Motor potentiometer
Ramp time
1 50 Hz/s 5 331 Advanced
Rate of change in the
motor potentiometer
reference when
increased or
decreased.
P3.17
Motor potentiometer
Copy ref.
0 1 0 1864 Advanced
In case MotPot is
alternated with Pre-
set.
0: Keep memory of
previous MotPot Ref
1: Start from actual
Ref
P3.18
Motor potentiometer
Reset
0 2 0 367 Basic
Motor potentiometer
frequency reference
reset logic.
0 = No reset
1 = Reset if stopped
or powered down
2 = Reset if powered
down
Table 32: Group References.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 20 SERIES and is the answer not in the manual?

Vacon 20 SERIES Specifications

General IconGeneral
Output Voltage0 to Input Voltage
Storage Temperature-40°C to +70°C
DimensionsVaries by model
WeightVaries by model
Power Range0.25 kW to 18.5 kW
Voltage Range200 V to 480 V
Control MethodSensorless vector control
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Communication OptionsModbus, CANopen
EMC FilterIntegrated
STO (Safe Torque Off)Yes
Input Voltage208-240 V, 380-480 V
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature
Operating Temperature-10°C to +50°C
Humidity5% to 95% non-condensing