vacon • 29 Description of Groups
2
2.2.13 Group Analogue output: Menu Par G13
2.2.14 Group User interface: Menu Par G14
Code Parameter Min Max Unit Default ID Level Description
P13.1 AO1 function 0 6 2 307 Service
0 = Not used (fixed 100%)
1 = Freq. reference (0-fmax)
2 = Output freq. (0 -fmax)
3 = Motor speed (0 - Speed
max)
4 = Output current (0-I
nMotor
)
5 = Motor torque (0-T
nMotor
)
6 = Motor power (0-P
nMotor
)
P13.2 AO1 minimum 0 1 0 310 Service
0 = 0V
1 = 2V
P13.3
AO1 Output
scale
0,0 1000,0 % 100.0 311 Service Scaling factor
P13.4 AO1 filter time 0.00 10.00 s 0.10 308 Service
Filtering time of analogue out-
put signal.
0 = No filtering
Table 42: Group Analogue output.
Code Parameter Min Max Unit Default ID Level Description
P14.1 Parameters access level 0 2 0 115 Basic
0 = Basic
1 = Advanced
2 = Service
P14.2 Parameters lock 0 1 0 1805 Basic
0 = Edit Enabled
1 = Edit Disabled