vacon • 19 Description of Groups
2
2.2.4 Group Ramps: Menu PAR G4
Code Parameter Min Max Unit Default ID Level Description
P4.1 Acceleration time 1 0.1 3000.0 s 3.0 103 Basic
Defines the time required
for the output frequency to
increase from zero fre-
quency to maximum fre-
quency
P4.2 Deceleration time 1 0.1 3000.0 s 3.0 104 Basic
Defines the time required
for the output frequency to
decrease from maximum
frequency to zero fre-
quency
P4.3 Ramp 1 shape 0.0 10.0 s 0.0 500 Basic Rounded speed profile.
P4.4 Acceleration time 2 0.1 3000.0 s 10.0 502 Advanced
Time from 0 to max fre-
quency
P4.5 Deceleration time 2 0.1 3000.0 s 10.0 503 Advanced
Time from 0 to max fre-
quency
P4.6 Ramp 2 shape 0.0 10.0 s 0.0 501 Advanced Rounded speed profile.
P4.7
Acceleration time 2
freq. threshold
0.00 P3.2 Hz 0.00 527 Advanced
Threshold for auto change
from acc1 to acc2
P4.8
Deceleration time 2
freq. threshold
0.00 P3.2 Hz 0.00 528 Advanced
Threshold for auto change
from dec2 to dec1
P4.9
Quick Stop dec.
time
0.1 3000.0 s 1.0 1889 Basic
Time from max frequency
to 0
Table 33: Group Ramps.