Parameter description vacon • 46
Service support: find your nearest Vacon service center at www.vacon.com
3
3.7 Mechanical brake
P7.1 BRAKE OPEN FREQUENCY
P7.2 BRAKE OPEN CURRENT
Thresholds that must be reached for external brake open at start.
If P7.1 > 0Hz, frequency reference is internally limited to P7.1 + 0.1 Hz until the brake is re-
leased.
Fault 56 Brake Time Out is triggered if the thresholds in P7.1 and P7.2 are not reached within
3s from Start command.
P7.3 B
RAKE CLOSE FREQUENCY
The brake is closed when the start command is low and output frequency is below this thresh-
old. Possible delay in P7.4.
P7.4 B
RAKE CLOSE DELAY
Respected in any stop condition (quick, fault, no enable), apart direct control from ASi input,
when the signal goes low.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 20 SERIES and is the answer not in the manual?

Vacon 20 SERIES Specifications

General IconGeneral
Output Voltage0 to Input Voltage
Storage Temperature-40°C to +70°C
DimensionsVaries by model
WeightVaries by model
Power Range0.25 kW to 18.5 kW
Voltage Range200 V to 480 V
Control MethodSensorless vector control
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Communication OptionsModbus, CANopen
EMC FilterIntegrated
STO (Safe Torque Off)Yes
Input Voltage208-240 V, 380-480 V
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature
Operating Temperature-10°C to +50°C
Humidity5% to 95% non-condensing

Related product manuals