vacon • 23 Description of Groups
2
2.2.8 Group Supervisions: Menu PAR G8
Code Parameter Min Max Unit Default ID Level Description
P8.1
Running Ok speed
tolerance
0.0 100.0 % 90.0 1880 Advanced
P8.2
Output frequency
supervision
0 2 2 315 Advanced
0 = not used
1 = Low limit
2 = High limit
P8.3
Frequency supervision
limit
0.00 P3.2 Hz 35.00 316 Advanced
Output frequency super-
vision threshold
P8.4
Current supervision
limit
0.00
2 x I
H
A 0.00 1811 Advanced
Current supervision
threshold
P8.5
Process display source
selection
0 4 1 1036 Advanced
Selection of variable pro-
portional to process:
0 = Output frequency
1 = Motor speed
2 = Motor torque
3 = Motor power
4 = Motor current
P8.6
Process display
decimal digits
0 3 1 1035 Advanced Decimals on display
P8.7
Process display max
value
0.0 3276.7 100.0 1034 Advanced
Process display max
value (it depends on
P7.11: with zero decimal
digit the max value is
32767; with 1 decimal
digit the max value is
3276.7)
Table 37: Group supervisions.