vacon • 43 Parameter description
3
P5.8 EXTERNAL FAULT, CLOSE
Fault is triggered by high signal.
P5.9 E
XTERNAL FAULT, OPEN
Fault is triggered by low signal.
P5.10 R
UN ENABLE
Motor stops by coasting if the signal is missing.
Note: The drive is not in Ready state when Enable is low.
P5.11 R
AMP TIME 2 SELECTION
Ramp 2 is selected by signal high.
P5.12 MOTOR POTENTIOMETER UP
Signal high causes speed increase.
P5.13 M
OTOR POTENTIOMETER DOWN
Signal high causes speed reduction.
P5.14 Q
UICK STOP OPEN
Signal low forces the drive to stop, ramping down with the time defined in P4.9.
To see description of P2.5 for details about the function.
P5.15 Q
UICK STOP CLOSE
Similar to P5.14, but in this case Quick Stop is activated by high signal.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon 20 SERIES and is the answer not in the manual?

Vacon 20 SERIES Specifications

General IconGeneral
Output Voltage0 to Input Voltage
Storage Temperature-40°C to +70°C
DimensionsVaries by model
WeightVaries by model
Power Range0.25 kW to 18.5 kW
Voltage Range200 V to 480 V
Control MethodSensorless vector control
Protection ClassIP20
Ambient Temperature-10°C to +50°C
Communication OptionsModbus, CANopen
EMC FilterIntegrated
STO (Safe Torque Off)Yes
Input Voltage208-240 V, 380-480 V
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Overtemperature
Operating Temperature-10°C to +50°C
Humidity5% to 95% non-condensing

Related product manuals