vacon • 61 Parameter description
3
3.12.1.2 Fieldbus Data OUT: Slave ->Master
Notes:
• Fieldbus different from Modbus have their own Status Word (see manual of the specific
fieldbus board).
Modbus
register
Name Description Range
2101 Status word Drive state
Binary coded:
b0: Ready
b1: Run
b2: Reverse
b3: Fault
b4: Warning
b5: Freq. reference reached
b6: Zero speed
2102 General Status word Drive state
b0: Ready
b1: Run
b2: Reverse
b3: Fault
b4: Warning
b5: Freq. reference reached
b6: AUTO mode
b7: MANUAL mode
b8: Brake command
2103 Actual speed(*) Actual speed
0...10000 as 0,00...100,00%
of Min freq. - Max freq.
range
2104 Fieldbus Data OUT 1 Programmable See P12.1
2105 Fieldbus Data OUT 2 Programmable See P12.2
2106 Fieldbus Data OUT 3 Programmable See P12.3
2107 Fieldbus Data OUT 4 Programmable See P12.4
2108 Fieldbus Data OUT 5 Programmable See P12.5
2109 Fieldbus Data OUT 6 Programmable See P12.6
2110 Fieldbus Data OUT 7 Programmable See P12.7
2111 Fieldbus Data OUT 8 Programmable See P12.8
Table 47. Modbus data outputs. They can vary depending on fieldbus used (See specific
fieldbus option board installation manual).