EasyManua.ls Logo

VAMP 210 - Residual Voltage Protection (59 N)

VAMP 210
94 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VAMP Ltd Generator protection relay
Technical description
VAMP 210
VM210.EN004 Vamp 24h support phone: +358 (0)20 753 3264
21
Parameters of the earth fault protection:
I
0
>, I
0
>> (50N/51N)
Parameter: Value/unit:
Measured
value
I
01
A Primary earth-fault current I
01
Display I
0
>, I
0
>> A Setting value I
0
I
0
>, I
0
>> pu Setting value
DT Definite time curve
NI, VI,
EI, LTI
Inverse time (I
0
>)
t>, t>> s
Operating time at definite time
function
Setting
values
k>
Time multiplier at inverse time
(I
0
>)
SCntr Cumulative start counter
TCntr Cumulative trip counter
Flt pu Max. fault value
Recorded
values
EDly %
Elapsed time as compared to the
set operating time, 100% =
tripping
I
02
>, I
02
>> (50N/51N)
Parameter: Value/unit:
Measured
value
I
02
A
Earth-fault current I
02
as primary
value.
Display I
02
>, I
02
>> A Start current in primary units
I
02
>, I
02
>> pu
Start current value in relation to
the rated current Io2n
t>, t>> s
Operating time at definite time
function
Setting
values
k> Time multiplier at inverse time
SCntr Cumulative start counter
TCntr Cumulative trip counter
Flt pu Max. fault value
Recorded
values
EDly %
Elapsed time as compared to the
set operating time, 100% =
tripping
2.2.6. Residual voltage protection (59N)
If the generator is connected to the power system via a unit
transformer, the stator earth-fault protection of the generator
is typically realized with a neutral overvoltage function. The
neutral voltage is measured with a voltage transformer
connected between the generator neutral and earth. The
neutral voltage function comprises two overvoltage stages, both
with separately adjustable definite time operation delays.

Table of Contents

Related product manuals